BS12094-1:2003

REQUIPMENT AND TEST FOR GAS EXTINGUISHING SYSTEM

BRITISH STANDARD BS EN
12094-1:2003
Fixed firefighting
systems—Components
for gas extinguishing
systems—
Part 1: Requirements and test methods
for electrical automatic control and
delay devices
The European Standard EN 12094-1:2003 has the status of a
BritishStandard
ICS 13.220.20
 







 
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIBS EN 12094-1:2003
This British Standard was
published under the authority
of the Standards Policy and
Strategy Committee
on30October2003
© BSI 30October2003
ISBN 0 580 42863 X
National foreword
This British Standard is the official English language version
ofEN12094-1:2003.
This European Standard is subject to transitional arrangements agreed under
a Commission mandate which is intended to lead to CE marking in support of
the Construction Products Directive. In order to allow for any changes in
national regulations, the Member States have agreed a transition period before
CE marking becomes effective, and this period will end in August 2006.
The UK participation in its preparation was entrusted by Technical Committee
FSH/18, Fixed fire fighting systems, to Subcommittee FSH/18/6, Gas
extinguishing systems, which has the responsibility to:
A list of organizations represented on this subcommittee can be obtained on
request to its secretary.
Cross-references
The British Standards which implement international or European
publications referred to in this document may be found in the BSI Catalogue
under the section entitled “International Standards Correspondence Index”, or
by using the “Search” facility of the BSI Electronic Catalogue or of British
Standards Online.
This publication does not purport to include all the necessary provisions of a
contract. Users are responsible for its correct application.
Compliance with a British Standard does not of itself confer immunity
from legal obligations.
—aid enquirers to understand the text;
—present to the responsible international/European committee any
enquiries on the interpretation, or proposals for change, and keep the
UK interests informed;
—monitor related international and European developments and
promulgate them in the UK.
Summary of pages
This document comprises a front cover, an inside front cover, the EN title page,
pages 2 to 44, an inside back cover and a back cover.
The BSI copyright notice displayed in this document indicates when the
document was last issued.
Amendments issued since publication
Amd. No. DateComments
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEUROPEAN STANDARD
NORME EUROPÉENNE
EUROPÄISCHE NORM
EN 12094-1
April 2003
ICS 13.220.20
English version
Fixed firefighting systems - Components for gas extinguishing
systems - Part 1: Requirements and test methods for electrical
automatic control and delay devices
Installations fixes de lutte contre l'incendie - Eléments
constitutifs pour installations d'extinction à gaz - Partie 1:
Exigences et méthodes d'essais applicables aux dispositifs
électriques automatiques de commande et de
temporisation
Ortsfeste Brandbekämpfungsanlagen - Bauteile für
Löschanlagen mit gasförmigen Löschmitteln - Teil 1:
Anforderungen und Prüfverfahren für automatische
elektrische Steuer- und Verzögerungseinrichtungen
This European Standard was approved by CEN on 9 January 2003.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the Management Centre has the same status as the official
versions.
CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece,
Hungary, Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands, Norway, Portugal, Slovakia, Spain, Sweden, Switzerland and United
Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36    B-1050 Brussels
© 2003 CENAll rights of exploitation in any form and by any means reserved
worldwide for CEN national Members.
Ref. No. EN 12094-1:2003 E
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
2
Contents
page
Foreword.....................................................................................................................................................................4
Introduction................................................................................................................................................................6
1Scope..............................................................................................................................................................7
2Normative references...................................................................................................................................7
3Terms, definitions and abbreviations.........................................................................................................7
3.1Terms and definitions...................................................................................................................................7
3.2Abbreviations................................................................................................................................................9
4Functional requirements............................................................................................................................10
4.1General.........................................................................................................................................................10
4.2Environmental class...................................................................................................................................10
4.3Signal processing and indication..............................................................................................................10
4.4Reception and processing of input triggering signals............................................................................13
4.5Transmission of extinguishing signal......................................................................................................14
4.6Activation of alarm devices........................................................................................................................14
4.7Indication of the supply with power..........................................................................................................14
4.8Activated condition.....................................................................................................................................14
4.9Indication of activated condition...............................................................................................................14
4.10Released condition.....................................................................................................................................15
4.11Indication of Released condition...............................................................................................................15
4.12Resetting of the Activated condition and the Released condition........................................................15
4.13Fault warning condition..............................................................................................................................15
4.14Indication of Fault warning condition.......................................................................................................16
4.15Disabled condition......................................................................................................................................17
4.16Indication of Disabled condition................................................................................................................18
4.17Delay of extinguishing signal (Option with requirements).....................................................................18
4.18Signal representing the flow of extinguishing agent (Option with requirements)...............................18
4.19Monitoring of the status of components (Option with requirements)...................................................18
4.20Emergency hold device (Option with requirements)...............................................................................19
4.21Control of flooding time (Option with requirements)..............................................................................19
4.22Initiation of secondary flooding (Option with requirements).................................................................20
4.23Manual only mode (Option with requirements)........................................................................................20
4.24Triggering signals to equipment within the system (Option with requirements).................................20
4.25Extinguishing signals to spare cylinders (Option with requirements)..................................................21
4.26Triggering of equipment outside the system (Option with requirements)............................................21
4.27Emergency abort device (Option with requirements).............................................................................21
4.28Control of extended discharge (Option with requirements)................................................................... 21
4.29Release of the extinguishing media for selected flooding zones (Option with requirements)...........22
4.30Activation of alarm devices with different signals (Option with requirements)...................................22
5Design requirements..................................................................................................................................22
5.1General.........................................................................................................................................................22
5.2Mechanical design......................................................................................................................................23
5.3Manual controls...........................................................................................................................................23
5.4Visible indicators.........................................................................................................................................23
5.5Audible indicators.......................................................................................................................................24
5.6Electrical design of components...............................................................................................................24
5.7Circuit design..............................................................................................................................................24
6Additional design requirements for software controlled e.c.d.s............................................................25
6.1General.........................................................................................................................................................25
6.2Software design...........................................................................................................................................25
6.3Program monitoring....................................................................................................................................25
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
3
6.4Storage of program and data......................................................................................................................25
6.5Monitoring of memory contents.................................................................................................................26
6.6Software documentation.............................................................................................................................26
6.7Operation of the e.c.d. in the event of a system fault..............................................................................27
7Marking.........................................................................................................................................................27
8Documentation.............................................................................................................................................27
9Tests..............................................................................................................................................................28
9.1General test requirements..........................................................................................................................28
9.2Functional tests............................................................................................................................................29
9.3Environmental tests.....................................................................................................................................31
9.4Damp heat, cyclic (Operational).................................................................................................................31
9.5Sulphur dioxide (SO2) corrosion (endurance)..........................................................................................32
10Evaluation of conformity.............................................................................................................................33
10.1General..........................................................................................................................................................33
10.2Initial type testing.........................................................................................................................................33
10.3Factory production control (FPC)..............................................................................................................34
Annex A (normative)  Summary of indications.......................................................................................................38
Annex B (informative)  Design requirements for software controlled e.c.d.........................................................39
Annex ZA (informative)  Clauses of this European Standard addressing the provisions of the EU
Construction Products Directive................................................................................................................40
ZA.0Scope of this annex.....................................................................................................................................40
ZA.1Relationship between EU Directive and this European Standard..........................................................40
ZA.2Procedure for the attestation of conformity of e.c.d.s.............................................................................40
ZA.3CE marking...................................................................................................................................................41
ZA.4EC certificate and declaration of conformity............................................................................................42
Bibliography..............................................................................................................................................................44
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
4
Foreword
This document (EN 12094-1:2003) has been prepared by Technical Committee CEN /TC 191, "Fixed firefighting
systems", the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an identical text or
by endorsement, at the latest by October 2003, and conflicting national standards shall be withdrawn at the latest
by April 2006.
This document has been prepared under a mandate given to CEN by the European Commission and the European
Free Trade Association, and supports essential requirements of EU Directive(s).
For relationship with EU Directive(s), see informative annex ZA, which is an integral part of this document.
This European Standard is part of a series concerned with gas extinguishing system components.
The following European Standards are planned to cover:
-  gas extinguishing systems (EN 12094)
-  sprinkler systems (EN 12259 and EN 12845)
-  powder systems (EN 12416)
-  explosion protection systems (EN 26184)
-  foam systems (EN 13565)
-  hose systems (EN 671)
-  smoke and heat control systems (EN 12101)
-  water spray systems1)
This European Standard has the general title "Fixed firefighting systems – Components for gas extinguishing
systems" and will consist of the following parts:
-  Part 1: Requirements and test methods for electrical automatic control and delay devices
-  Part 2: Requirements and test methods for non-electrical automatic control and delay devices
-  Part 3: Requirements and test methods for manual triggering and stop devices
-  Part 4: Requirements and test methods for container valve assemblies and their actuators
-  Part 5: Requirements and test methods for high and low pressure selector valves and their actuators for CO2
systems
-  Part 6: Requirements and test methods for non electrical disable devices for CO2 systems
-  Part 7: Requirements and test methods for nozzles for CO2 systems
                                                    
1)under preparation
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
5
-  Part 8: Requirements and test methods for flexible connectors for CO2 systems
-  Part 9: Requirements and test methods for special fire detectors
-  Part 10: Requirements and test methods for pressure gauges and pressure switches
-  Part 11: Requirements and test methods for mechanical weighing devices
-  Part 12: Requirements and test methods for pneumatic alarm devices
-  Part 13: Requirements and test methods for check valves and non-return valves
-  Part 16: Requirements and test methods for odorizing devices for CO2 low pressure systems
-  Part 17: Pipe hangers
-  Part 20: Requirements and test methods for compatibility of components
Annex A is normative. Annex B is informative.
This document includes a Bibliography.
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following
countries are bound to implement this European Standard: Austria, Belgium, Czech Republic, Denmark, Finland,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands, Norway, Portugal,
Slovakia, Spain, Sweden, Switzerland and the United Kingdom.
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
6
Introduction
It has been assumed in the preparation of this standard that the execution of its provisions is entrusted to
appropriately qualified and experienced people.
All pressure data in this European Standard are given as gauge pressures in bar, unless otherwise stated.
NOTE1 bar = 105
 N m-2
 = 100 kPa.
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
7
1 Scope
This European Standard specifies requirements and test methods for electrical automatic control and delay devices
(e.c.d.) for use in combination with automatic fire detection and fire alarm systems and CO2-, Inert Gas- or
Halocarbon Gas-Fire Extinguishing Systems installed in buildings.
The standard specifies compulsory functions which shall be provided on all electrical automatic control and delay
devices and optional functions (options with requirements) which may be provided.
Additional functions associated with fire extinguishing can be provided, but are not covered by this standard.
2 Normative references
This European Standard incorporates by dated or undated references, provisions from other publications. These
normative references are cited at the appropriate places in the text, and the publications are listed hereafter. For
dated references, subsequent amendments to or revisions of any of these publications apply to this European
Standard only when incorporated in it by amendment or revision. For undated references the latest edition of the
publication referred to applies (including amendments).
EN 54-1, Fire detection and fire alarm systems - Part 1: Introduction.
EN 54-2, Fire detection and fire alarm systems - Part 2: Control and indicating equipment.
EN 54-4, Fire detection and fire alarm systems - Part 4: Power supply equipment.
EN 12094-2, Fixed firefighting systems - Components for gas extinguishing systems - Part 2: Requirements and
test methods for non-electrical automatic control and delay devices.
EN 60068-1,  Environmental testing - Part 1: General and guidance (IEC 60068-1:1988 + Corrigendum 1988 +
A1:1992) .
EN 60068-2-30, Environmental testing – Part 2: Tests - Test Db and guidance: Damp heat, cyclic (12 + 12-hour
cycle) (IEC 60068-2-30:1980 + A1:1985).
prEN 60068-2-42, IEC 60068-2-42: Environmental testing - Part 2-42: Test methods; Test Kc: Sulphur dioxide test
for contacts and connections
EN 60529, Degrees of protection provided by enclosures (IP-Codes) (IEC 60529:1989).
EN 60721-3-3,  Classification of environmental conditions - Part 3: Classification of groups of environmental
parameters and their severities - Section 3: Stationary use at weather-protected locations (IEC 60721-3-3:1994).
3 Terms, definitions and abbreviations
3.1 Terms and definitions
For the purposes of this European Standard the following terms and definitions apply.
3.1.1
access level
one of several states of an e.c.d. as defined in EN 54-2
NOTEIn the access levels 1 to 4:
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
8
- selected controls can be operated;
- selected manual operations can be carried out;
- selected indications are visible;
- selected information can be obtained.
3.1.2
alphanumeric display
indicator capable of giving information by the display of messages consisting of text and/or numeric characters
3.1.3
condition
defined status of the e.c.d. or of the gas extinguishing system, which is indicated at the e.c.d.
NOTE 1The conditions of the e.c.d. recognised in this European Standard are the following:
- Activated Condition, when the commencing of the extinguishing control sequence is indicated;
- Pre-activated Condition, when the first of two necessary input triggering signals is indicated;
- Fault Warning Condition, when a fault is indicated;
- Disabled Condition, when the disablement of functions is indicated;
- Released Condition, when the flow of the extinguishing agent into the protected room or area is indicated;
- Quiescent Condition, when the e.c.d. is powered by power supply conforming to EN 54-4 and no other condition
status of the e.c.d. is indicated.
NOTE 2In some European countries in the quiescent condition the automatic/manual mode is indicated.
NOTE 3The following condition of the gas extinguishing system is recognised in this European Standard:
- Blocked Condition, when the non-electrical disable device prevents the release of the extinguishing agent.
3.1.4
earth fault
unwanted connection between earth potential and any part of the e.c.d., transmission paths to the e.c.d., or
transmission paths between parts of the e.c.d.
3.1.5
field
subdivision of a window
3.1.6
indication
information given by an indicator
3.1.7
indicator
device which can change its state to give information
3.1.8
module
independent part of the program which fulfils specified functions
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
9
3.1.9
monitoring
supervision of the operational condition of electrical and non-electrical components of the extinguishing system
3.1.10
non-volatile memory
memory element that does not require the presence of an energy source for the retention of its contents
3.1.11
pre-discharge-warning time
time period between the start of the warning indication and the discharge to warn personnel of impending gas
release
3.1.12
program
software necessary for an e.c.d. to comply with the requirements of this standard
NOTESoftware includes e.g. initializing data, reset and interrupt vectors, operating code, declarations.
3.1.13
reset
operation capable of terminating the indication of the "Activated Condition", "Released Condition" or the "Fault
Warning Condition"
3.1.14
running data
alterable data subject to temporary modification during operation either automatically or by manual controls
3.1.15
silencing
manual operation to switch off the audible signal of a sounding device which is capable of being automatically
resounded by a new event
3.1.16
site specific data
alterable data required for operation in a defined system configuration
3.1.17
transmission path
physical connection, external to the enclosure of the e.c.d., for the transmission of information and/or power
NOTEExamples are the connections:
- from or to a c.i.e. of a fire detection and fire alarm system, and/or
- from or to devices connected within the extinguishing system.
3.1.18
volatile memory
memory element that requires the presence of an energy source for the retention of its content
3.1.19
window
part or all of an alphanumeric display used for information relating to one condition at a given time
NOTEA subdivision of the display can be realised either by mechanical separation, or under software control.
3.2 Abbreviations
For the purposes of this European Standard, the following abbreviations apply:
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
10
3.2.1
c.i.e.
control and indication equipment of an automatic fire detection and fire alarm system
3.2.2
e.c.d.
electrical automatic control and delay device
3.2.3
f.d.a.s.
fire detection and fire alarm system
3.2.4
p.s.e.
power supply equipment
4 Functional requirements
4.1 General
The e.c.d. shall be either a separate device or part of a c.i.e.
If the e.c.d. is part of a c.i.e., functions and indications required for the e.c.d. and the c.i.e., that are common to
both, may be executed using the same component. In this case the requirements of this European Standard and
that for the c.i.e. (see EN 54-2) shall be fulfilled.
The e.c.d. shall be powered by power supply equipment in accordance with EN 54-4.
Concerning the compulsory functions and the provided optional functions, the e.c.d. shall conform to the
requirements in clauses 4, 5 and 6 together with those in 9.3 (environmental tests).
If the e.c.d. provides any of the optional functions the manufacturer shall specify which options are provided, see
8.2. The e.c.d. including these options shall be subjected to the testing and shall meet the requirements of this
European Standard.
4.2 Environmental class
The e.c.d. shall be classified and specified by the manufacturer for one of the classes as indicated below
depending upon the intended ambient conditions:
- Class A: temperature range of - 5 °C to + 40 °C;
- Class B: temperature range of – 20 °C to + 50 °C;
- Class C: temperature range of - 5 °C to + 40 °C and corrosive atmosphere class 3C4 of EN 60721-3-3;
- Class D: temperature range of - 20 °C to + 50 °C and corrosive atmosphere class 3C4 of EN 60721-3-3.
4.3 Signal processing and indication
4.3.1 General
The e.c.d. shall be designed to receive, process and indicate signals for each flooding zone.
All processing of the functions necessary for the electrical control of the fire extinguishing installation shall be
carried out by the e.c.d..
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
11
4.3.2 Compulsory and optional functions
The e.c.d. shall be able to carry out the following compulsory functions (see also Figure 1):
a) Reception and processing of at least one input triggering signal from an f.d.a.s. and an input triggering signal
from manual triggering device(s) connected directly to the e.c.d. (see also 4.4);
b) On receipt of the input triggering signal(s), transmission of the extinguishing signal (see also 4.5, 4.3.2 g) and
4.17);
c) On receipt of the input triggering signal(s) activation of alarm devices (see also 4.6);
d) Indication of each condition unambiguously e.g. activated condition, fault warning condition (see also 4.7 to
4.16);
e) Transmission of the information of the incorrect status of components as specified in 4.19 (monitoring), if
provided, and of the information of the fault warning condition (see also 4.14 and 4.19);
f) Transmission of the information of the released condition (see also 4.11);
If the information is transmitted to automatic routing equipment E as defined in EN 54-1 the transmission to E
shall be indicated visibly at access level 1 by a separate light emitting indicator and/or by an alphanumeric
display in a clearly identifiable way.
Key
1Fire detection and fire alarm system (f.d.a.s.)
2Electrical control device (e.c.d.)
3Release equipment
NOTEFunctions a) to f) per flooding zone; outputs e) and f) at least common for each function. The indicator f) is only
compulsory in the case of a connection as specified in EN 54-1.
Figure 1 — Compulsory functions
The e.c.d. may be able to carry out the following optional functions (options with requirements), (see also Figure 2):
g) Delay the extinguishing signal (see 4.3.2 b)) for a given period of time which is known as a pre-discharge-
warning time (see also 4.17);
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
12
h) Reception of a signal representing the flow of the extinguishing agent (see also 4.18);
i) Monitoring of the status of components (e.g. weighing devices, valve positions), (see also 4.3.2 e) and 4.19);
j) Reception of signals from an emergency hold device (see also 4.20);
If this option is used, means shall be provided to transmit the information concerning the activation of the
emergency hold device.
k) Separate monitoring of the status of non-electrical disable device(s) (see also 4.3.2 e) and 4.19);
If this option is used, means shall be provided to transmit the information concerning the blocked position.
l) Control of flooding time, for instance in the case of low pressure CO2 systems (see also 4.21);
m) Initiating of a secondary flooding, for instance in the case of low pressure CO2 systems, including the reception
of a signal from a manual control device (see also 4.22);
n) Reception of signals from ancillary devices on the change over from manual only mode to automatic/manual
mode and vice versa (see also 4.23);
If this option is used, means shall be provided to transmit the information concerning the change over.
o) Transmission of a triggering signal to equipment within the fire extinguishing system (e.g. pilot cylinders,
optical warning devices) (see also 4.24);
p) Transmission of extinguishing signals to spare cylinders or spare cylinder banks (see also 4.25);
If a main and a spare bank is provided, it shall be indicated on the e.c.d. that the spare bank will be activated in
case of alarm. The indication shall be given at access level 1 by a physically separated light emitting indicator
or by an alphanumeric display.
q) Transmission of signals to equipment outside the fire extinguishing system (triggering of doors, ventilation shut
down, plant shut down etc.) (see also 4.26);
r) Reception of signals from emergency abort device (see also 4.27);
If this option is used, means shall be provided to transmit the information concerning the activation of the
emergency abort device.
s) Control of an extended discharge, for instance in the case of low pressure CO2 systems (see also 4.28);
t) Release of the extinguishing media for selected flooding zones (see also 4.29);
u) Activation of alarm devices with different signals (see also 4.30).
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
13
Key
1Electrical control device (e.c.d.)
NOTE 1Functions g) to u) per flooding zone; outputs j), k), n) and r) at least common for each function.
NOTE 2Functions g), t) and u) are optional extensions of the compulsory functions a), b) and c).
NOTE 3Functions l) and m) can be provided in combination with the compulsory function b).
Figure 2 — Optional functions g) to u)
4.4 Reception and processing of input triggering signals
NOTEThis subclause relates to 4.3.2 a).
4.4.1 The e.c.d. shall be designed to receive and process at least one triggering signal from an f.d.a.s. and a
triggering signal from manual triggering device(s) connected directly to the e.c.d.
NOTEIn some European countries there are national regulations requiring that the activated condition can only be
established after the reception of two input triggering signals from two independent transmission paths between a c.i.e. of an
f.d.a.s. and the e.c.d.
4.4.2 The processing of the input triggering signal shall have the highest priority unless
-  the signal from an emergency hold or abort device is present or
-  a fault of the transmission path to the emergency hold or abort device is present or
-  the disabled condition is present or
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
14
-  the release of extinguishing media is to be prevented in accordance with 4.29.
If the processing of the input triggering signal has started, no disablement shall be possible for the appropriate
flooding zone.
4.5 Transmission of extinguishing signal
NOTEThis subclause relates to 4.3.2 b).
The e.c.d. shall be designed, on receipt of the input triggering signal, to transmit the extinguishing signal (see also
4.3.2 g) and 4.17).
4.6 Activation of alarm devices
NOTEThis subclause relates to 4.3.2 c).
4.6.1 The e.c.d. shall be designed, on receipt of the input triggering signal, to activate alarm devices.
4.6.2 If a silencing function is provided, after activation the alarm devices shall only be capable of being silenced
manually at access level 2, after establishment of the released condition.
4.7 Indication of the supply with power
4.7.1 The e.c.d. shall be designed so that the supply with power is indicated unambiguously.
4.7.2 A visible indication shall be given at access level 1 by means of a separate light emitting indicator while the
e.c.d. is supplied with power (see also annex A).
4.8 Activated condition
4.8.1 The e.c.d. shall enter the activated condition within a time specified by the manufacturer up to a maximum
of 3 s after the activation of a manual triggering device connected directly to the e.c.d. or the activation of a
transmission path from an f.d.a.s.
The manufacturer may specify a time shorter than 3 s. In this case, this specification shall be tested and verified.
4.8.2 After establishing the activated condition all appropriate outputs shall be triggered within a time specified by
the manufacturer up to a maximum of 1 s unless a time delay is interposed in an output function circuit (see 4.17).
The manufacturer may specify a time shorter than 1 s. In this case, this specification shall be tested and verified.
4.9 Indication of activated condition
NOTEThis subclause relates to 4.3.2 d) and see annex A.
4.9.1 The activated condition shall be indicated unambiguously without any prior manual intervention by:
a) an audible indication and
b) visible indications for each flooding zone at access level 1 by one or both of the following means:
1) physically separated light emitting indicators;
2) an alphanumeric display.
4.9.2 The audible indication shall be capable of being silenced manually at access level 1 or 2 by an operation
separate from the reset function. It shall not be silenced automatically.
Each new alarm signal from another zone shall cause the audible indication again (see also 4.14.10).
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
15
4.9.3 If the activated condition is established only after the reception of two input triggering signals from an
f.d.a.s, the reception of the first signal shall be indicated visibly and audibly as the pre-activated condition. On
reception of the first signal, outputs (e.g. for plant shut down) may be activated.
For the indication of the pre-activated condition, the same indicators may be used as for the indication of the
activated condition. If the same light emitting indicator is used, the reception of the first signal shall be indicated
with flashing light, the activated condition with steady light.
4.10 Released condition
The released condition shall be established upon reception of a signal representing the flow of the extinguishant or
upon the triggering of the extinguishing signal output.
4.11 Indication of Released condition
NOTEThis subclause relates to 4.3.2 d) and 4.3.2 f) and see annex A.
4.11.1 The released condition shall be indicated unambiguously without any prior manual intervention by visible
indications for each flooding zone at access level 1 by one or both of the following means:
-  physically separated light emitting indicators;
-  an alphanumeric display.
When the released condition is established upon reception of a signal representing the flow of extinguishant
without the activated condition, the released condition shall also be indicated audibly.
The audible indication shall be capable of being silenced manually at access level 1 or 2 by an operation separate
from the reset function. It shall not be silenced automatically.
4.11.2 The e.c.d. shall provide an output signalling the "Released Condition".
If the information is transmitted to automatic routing equipment E as defined in EN 54-1 the transmission to E shall
be indicated visibly at access level 1 by a separate light emitting indicator and/or by an alphanumeric display in a
clearly identifiable way.
4.12 Resetting of the Activated condition and the Released condition
4.12.1 The activated condition and the released condition shall be capable of being reset, except as required in
4.12.2, at access level 2. The same element may be used as for terminating the fault warning condition. Following
the reset operation the indication of the correct conditions, corresponding to any received signals, shall either
remain or be re-established within 20 s.
4.12.2 Technical means shall be provided to inhibit the reset function after establishing the activated condition
either for an adjustable time period up to 30 min or until the reception of a signal representing the end of discharge.
The setting is restricted to access level 3. The adjusted time shall be indicated at least at access level 3 (e.g. label).
4.13 Fault warning condition
4.13.1 The e.c.d. shall be capable of recognising and indicating in a clearly identifiable way the following as a
"Fault Warning Condition”, if the function is provided, within 100 s of their occurrence unless otherwise specified in
this standard.
NOTEThe value of 100 s is chosen in accordance with EN 54-2.
a) Short circuit or interruption in a transmission path for the reception of input triggering signal(s) from an f.d.a.s.;
b) Short circuit or interruption in a transmission path to the actuators and additional non-electrical control and
delay devices (see EN 12094-2) (e.g. mechanical), if the additional control device is not in the same cabinet as
the electrical one;
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
16
c) Short circuit or interruption in a transmission path to alarm devices;
d) Short circuit or interruption in a transmission path to manual controls (e.g. emergency hold device, emergency
abort device, manual triggering device) (see also 4.20 or 4.27 respectively);
e) Short circuit or interruption in a transmission path to a non-electrical disable device;
f) Short circuit or interruption in the transmission path for monitoring of components relevant for the proper
function of the extinguishing installation;
g) Short circuit or interruption in the transmission path for the reception of the signal representing the flow of the
extinguishing agent;
h) Short circuit or interruption in the transmission path to fault warning routing equipment as specified in EN 54-1
(J);
i) Short circuit or interruption in the transmission path to fire alarm routing equipment as specified in EN 54-1 (E);
j) Power supply faults:
1) Faults of power supplies as defined in EN 54-4;
2) Short circuit or interruption of transmission paths carrying power between the e.c.d. and the power
supply, if these transmission paths are outside the e.c.d. cabinet and outside the power supply cabinet
and where the transmission path between the two cabinets exceeds 0,1 m. In this case, in addition,
provision shall be made for two separate transmission paths from the power supply to the e.c.d. such that
a short circuit or interruptions in one of the transmission paths does not prevent the supply of power to the
e.c.d. Transmission paths between the e.c.d. and the power supply, which are outside the e.c.d. cabinet
and outside the power supply cabinet and where the transmission path is up to 0,1 m, shall be
mechanically protected (e.g. by a steel pipe);
k) Earth fault which affects the function of the e.c.d.;
l) Rupture of a fuse or operation of any protective device that would prevent the operation of the e.c.d.;
m) Incorrect execution of the operating program and/or corruption of the memory content (see clause 6, only in
case of a software controlled e.c.d.).
4.13.2 The fault warning condition shall be capable of being reset manually or automatically. Manual reset shall be
restricted to access level 2. The same element may be used as for resetting the released condition. Following the
reset operation the indication of the correct conditions, corresponding to any received signals, shall either remain or
be re-established within 20 s.
NOTEThe value of 20 s is chosen in accordance with EN 54-2.
4.14 Indication of Fault warning condition
NOTE 1This subclause relates to 4.3.2 d) and 4.3.2 e).
NOTE 2See also 5.7 and 6.7.
4.14.1 Faults as under 4.13.1 shall be indicated automatically and unambiguously at the e.c.d. in the following
manner:
a) an audible indication; and
b) a visible indication by means of a light emitting indicator at access level 1;
Faults on a transmission path for 4.13.1 a) to g) covering one flooding zone shall be indicated at least as a
common fault of that flooding zone.
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
17
Faults on a transmission path for 4.13.1 a) to g) covering more than one flooding zone shall be indicated at
least as a fault of that transmission path.
4.14.2 For faults as under 4.13.1a), b), c), d), e), f) and g) the affected transmission path shall be identified by a
signal of a separate light emitting indicator for each transmission path or by means of an alphanumeric display at
access level 1, 2 or 3.
4.14.3 For faults as under 4.13.1 h) and i) the affected transmission path shall be identified by a signal of a
separate light emitting indicator or by means of an alphanumeric display at access level 1.
4.14.4 Faults as under 4.13.1 j) shall be indicated by a signal of a separate light emitting indicator or by means of
an alphanumeric display at least as a common indication for all mentioned power supply faults at access level 1.
4.14.5 Faults as under 4.13.1 k) shall be indicated by a signal of a separate light emitting indicator or by means of
an alphanumeric display at least as a common indication for all earth faults at access level 1, if not covered by
another fault indication.
4.14.6 Faults as under 4.13.1 l) shall be indicated at least as a fault of the supervised function as e.g. "Power
Supply Fault".
4.14.7 Faults as under 4.13.1 m) shall be indicated by a signal of a separate light emitting indicator or by means of
an alphanumeric display at access level 1 per flooding zone, or in case of fully redundant techniques per e.c.d.
(see also 5.7.1).
This fault indication shall remain until manual reset and/or another manual operation.
4.14.8 Faults which have been detected but cannot be displayed because of limited space of the used
alphanumeric display shall be capable of being indicated by manually initiated scrolling at access level 1 or 2.
If more faults have been detected than can be simultaneously indicated, this shall be indicated.
4.14.9 The indication of the fault warning indicator for each flooding zone common for the flooding zone faults
shall not be suppressed by any other status indications of the e.c.d. (e.g. "Activated Condition").
4.14.10 The audible signal shall be capable of being silenced manually at access level 1 or 2. The audible signal
shall be silenced automatically, if the control device has been reset automatically from the fault warning condition to
the quiescent condition, except faults as under 4.13.1m).
4.14.11 Each new fault shall cause the audible signal again. The audible signal may be different from the signal of
the activated condition. If they are different the signal for the "Activated Condition" shall have priority.
4.14.12 The e.c.d. shall provide an output in accordance with 4.3.2 e). This signal shall be given even if the e.c.d. is
deenergised.
4.15 Disabled condition
4.15.1 The e.c.d. shall at least be capable of disabling and re-enabling for each flooding zone the following by
separate manual operation at access level 2.
a) the function of processing alarm signals received via the transmission path(s) to a f.d.a.s., if the manual only
mode is not provided.
b) the function of processing alarm signals received via the transmission path(s) to manual triggering devices.
c) output signal(s) and/or transmission path(s) to actuators and associated triggering signals to activate the
outputs mentione, d in 4.3.2 e) and f).
d) output signal(s) and/or transmission path(s) for triggering of equipment outside the fire extinguishing system
(triggering of doors, ventilation shut down, plant shut down etc.), if such outputs are provided.
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
18
The released condition shall not be reached when the actuators are disabled, unless the signal representing the
flow of extinguishant is received, see 4.18.3.
4.15.2 Disablement shall not be affected by a reset function.
Disabling of the transmission path to the alarm devices of a flooding zone shall be possible only in combination with
the disabling of the transmission path to the actuators of that flooding zone.
4.15.3 Provision shall be made so that the enabling of a function and/or transmission path shall not produce a
signal to the actuators with the consequence of a direct release of the extinguishing agent.
The enabling of a function and or transmission path to actuators during the presence of an alarm signal in the
disabled condition shall not release the extinguishing agent without the elapsing of the predetermined pre
discharge warning time.
4.16 Indication of Disabled condition
NOTEThis subclause relates to 4.3.2 d).
The disablement as described in 4.15 shall be indicated at access level 1 for each flooding zone within 2 s
unambiguously by means of:
-  separate light emitting indicators for each disablement or
-  an alphanumeric display.
4.17 Delay of extinguishing signal (Option with requirements)
NOTEThis subclause relates to 4.3.2 g).
4.17.1 The e.c.d. may provide technical means to delay the transmission of the extinguishing signal (see 4.3.2 b))
for a given period of time which is known as a pre-discharge-warning time.
4.17.2 The delay time of the e.c.d. shall be adjustable for a delay time from 0 s up to a maximum of 60 s. The
setting shall be done in steps of maximum 5 s and shall be restricted to the access level 3. The adjusted delay time
shall be indicated at least at access level 3 (e.g. label).
4.17.3 The set delay time shall not be affected by other components like fire detection and alarm devices.
4.17.4 The set delay time shall remain within deviation limits of ± 10% of the set value.
4.18 Signal representing the flow of extinguishing agent (Option with requirements)
NOTEThis subclause relates to 4.3.2 h).
4.18.1 The e.c.d. may be designed to receive a signal representing the flow of the extinguishing agent.
4.18.2 Concerning the transmission paths for signals representing the flow of the extinguishing agent, the
requirements of 4.13 and 4.14 shall be satisfied.
4.18.3 Upon reception of a signal representing the flow of extinguishant without the activated condition the
released condition shall be established and the e.c.d. shall activate all appropriate outputs as required in 4.8.2.
4.19 Monitoring of the status of components (Option with requirements)
NOTEThis subclause relates to 4.3.2 i) and 4.3.2 k).
4.19.1 The e.c.d. may be designed to monitor the status of components.
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
19
4.19.2 Incorrect status of components, e.g. loss of agent, shall be indicated within 100 s of its occurrence by an
audible indication and by a visible indication at access level 1 by a separate light emitting indicator or alphanumeric
display at least as a common indication and shall activate the output as required in 4.3.2 e).
NOTENational guidelines for planning and installation can require e.g. a separate indicator per flooding zone or a
maximum number of monitored components per indicator.
4.19.3 The blocked position of the non-electrical disable device shall be indicated by visible indications for each
flooding zone at access level 1 by one or both of the following means:
a) physically separated light emitting indicators;
b) an alphanumeric display.
Means shall be provided to transmit the information concerning the blocked position.
The normal transition of the non-electrical disable device from the operational position to the blocked position shall
not result in an activation of the output as required in 4.3.2 e).
An indication and activation of the output as required in 4.3.2 e) shall be given if the non-electrical disable device
remains in a position which is neither the fully operational nor blocked (see 4.19.2).
4.20 Emergency hold device (Option with requirements)
NOTEThis subclause relates to 4.3.2 j).
4.20.1 The e.c.d. may provide technical means to connect emergency hold devices.
4.20.2 The signal of the emergency hold device shall not influence the extinguishing signal once established.
4.20.3 By the operation of the emergency hold device one of the following function sequences shall be started:
a) The extinguishing signal shall not be activated as long as the emergency hold device is continuously operated.
De-activation of the operation of the emergency hold device after the end of the specified pre-discharge
warning time shall cause the transmission of the extinguishing signal immediately. The pre-discharge warning
time shall not be interrupted, shortened or reset by the signal from the emergency hold device. Activation of
the emergency hold device shall be indicated visibly and audibly (if audible indication was silenced before) at
the e.c.d. The visible indication shall be given at access level 1 by means of a separate light emitting indicator
for each flooding zone and shall remain until manual reset.
b) The extinguishing signal shall not be activated while the emergency hold device is continuously operated. The
pre-discharge warning time shall be re-started from the beginning by each release of the emergency hold
device. The activation of the emergency hold device during the pre-discharge warning time shall be indicated
in the protected area by a change of the signal to the alarm devices.
NOTEThe intention of this is to provide a different audible signal from that given during the pre-discharge time delay
period and the released condition.
Activation of the emergency hold device shall be indicated visibly and audibly (if audible indication was
silenced before) at the e.c.d. The visible indication shall be given at access level 1 by means of a separate
light emitting indicator for each flooding zone while the emergency hold device is activated.
4.20.4 Faults of the transmission path to the emergency hold device shall be recognised and indicated within 2 s
and prevent the transmission of the extinguishing signal.
4.20.5 If an emergency hold function is provided, the e.c.d. shall have at least a common output able to transmit
the information of the activation of the emergency hold device.
4.21 Control of flooding time (Option with requirements)
NOTEThis subclause relates to 4.3.2 l).
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
20
4.21.1 The e.c.d. may be designed to control the flooding time, for instance in the case of low pressure CO2
systems.
4.21.2 If the e.c.d. is intended to control the flooding time, e.g. in CO2 low pressure systems, the flooding time
shall be adjustable from a minimum time specified by the manufacturer up to at least 300 s. The setting shall be
done in steps of maximum 5 s and is restricted to the access level 3. The adjusted flooding time shall be indicated
at least at access level 3 (e.g. label).
4.21.3 The set flooding time shall not be affected by other components like fire detection and alarm devices.
4.21.4 The set flooding time shall remain within deviation limits of ± 10% of the set value.
4.21.5 If the e.c.d. is intended to control the flooding time, means shall be provided which for test purposes allow
the termination of an already running flooding time. This shall only be possible by means of a separate manual
control at access level 3. The operation shall have no effect on the intended operation of the e.c.d. after this test.
4.22 Initiation of secondary flooding (Option with requirements)
NOTEThis subclause relates to 4.3.2 m).
4.22.1 The e.c.d. may be designed to initiate a secondary flooding, for instance in the case of low pressure CO2
systems, including the reception of a signal from a manual triggering device specifically for this function.
4.22.2 A secondary flooding shall not be initiated when the manual triggering device is operated during the normal
flooding. Upon operation of the manual triggering device after completion of the normal extinguishing sequence,
the initiation of a secondary flooding shall only be possible when the alarm sounders are not yet silenced. In this
case the secondary flooding shall be initiated immediately after the operation of this special manual triggering
device.
NOTEIf the alarm sounders have been silenced or the system was reset this special manual triggering device has no
function.
4.23 Manual only mode (Option with requirements)
NOTEThis subclause relates to 4.3.2 n).
4.23.1 The e.c.d. may be designed to change over from manual only mode to automatic/manual mode and vice
versa.
4.23.2 The status of the manual only mode shall be indicated visibly on the e.c.d. and an output shall be provided
that is able to transmit the information about this mode.
Changing of the mode shall be possible by manual operation at access level 2 or upon an input signal (e.g. from a
key switch).
The visible indication shall be given for each flooding zone at access level 1 by one or both of the following means:
-  physically separated light emitting indicators;
-  an alphanumeric display.
During the manual only mode, the activation of the e.c.d. shall only be possible by signals from manual triggering
devices.
4.24 Triggering signals to equipment within the system (Option with requirements)
NOTEThis subclause relates to 4.3.2 o).
4.24.1 The e.c.d. may be designed to transmit triggering signals to equipment within the fire extinguishing system
(e.g. pilot cylinders, optical warning devices).
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
21
4.24.2 Concerning the transmission paths for triggering signals to equipment within the system, the requirements
of 4.13 to 4.16 shall be satisfied.
4.25 Extinguishing signals to spare cylinders (Option with requirements)
NOTEThis subclause relates to 4.3.2 p).
4.25.1 The e.c.d. may be designed to transmit extinguishing signals to spare cylinders or spare cylinder banks.
4.25.2 If a main and a spare bank are provided, it shall be indicated on the e.c.d. that the spare bank will be
activated in case of alarm. The indication shall be given at access level 1 by a physically separated light emitting
indicator or by an alphanumeric display.
4.25.3 Concerning the transmission paths for extinguishing signals to spare cylinders, the requirements of 4.13 to
4.16 shall be satisfied.
4.26 Triggering of equipment outside the system (Option with requirements)
NOTEThis subclause relates to 4.3.2 q).
4.26.1 The e.c.d. may be designed to transmit triggering signals to equipment outside the fire extinguishing
system (triggering of doors, ventilation shut down, plant shut down etc.).
4.26.2 Concerning the transmission paths for triggering signals to equipment outside the system, the requirements
of 4.15 and 4.16 shall be satisfied.
4.27 Emergency abort device (Option with requirements)
4.27.1 The e.c.d. may provide technical means to connect emergency abort devices.
4.27.2 During the quiescent and activated condition the activation of the emergency abort device shall inhibit the
extinguishing signal until the emergency abort device has been deactivated and the e.c.d. has been reset from the
activated condition.
NOTEAfter activation the emergency abort device is latched.
4.27.3 Faults of the transmission path to the emergency abort device shall be recognised and indicated within 2 s
and prevent the transmission of the extinguishing signal.
4.27.4 Activation of the emergency abort device shall be indicated visibly and audibly (if audible indication was
silenced before) at the e.c.d. The visible indication shall be given at access level 1 by means of a separate light
emitting indicator for each flooding zone and shall remain until manually reset.
4.27.5 If an emergency abort function is provided, the e.c.d. shall have at least a common output able to transmit
the information of the activation of the emergency abort device.
4.28 Control of extended discharge (Option with requirements)
NOTE 1This subclause relates to 4.3.2 s).
NOTE 2During the normal flooding time the design quantity of extinguishant is discharged into the flooding zone and the
design concentration is built up. In some cases this concentration is to be maintained over a longer time (e.g. 10 min, 20 min).
This can be supported by a so called "extended discharge". During the extended discharge flooding time, the concentration is
maintained by a small flow of extinguishant through a separate extended discharge pipework into the flooding zone.
4.28.1 The e.c.d. may be designed to control an extended discharge, for instance in the case of low pressure CO2
systems.
4.28.2 If the e.c.d. is intended to control an extended discharge, e.g. in CO2 low pressure systems, the extended
discharge flooding time shall be adjustable up to at least 20 min. The setting shall be done in steps of maximum Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
22
1 min and is restricted to the access level 3. The adjusted extended discharge flooding time shall be indicated at
least at access level 3 (e.g. label).
4.28.3 The set extended discharge flooding time shall not be affected by other components like fire detection and
alarm devices.
4.28.4 The set extended discharge flooding time shall remain within deviation limits of ± 10 % of the set value.
4.28.5 If the e.c.d. is intended to control an extended discharge, means shall be provided which for test purposes
allow the termination of an already running extended discharge flooding time. This shall only be possible by means
of a separate manual control at access level 3. The operation shall have no effect on the intended operation of the
e.c.d. after this test.
4.29 Release of the extinguishing media for selected flooding zones (Option with requirements)
NOTE 1This subclause relates to 4.3.2 t).
NOTE 2In some cases, e.g. selector valves, it can be sensible after having established the released condition in one
flooding zone to prevent the release of the extinguishing media for other flooding zones.
4.29.1 The e.c.d. may provide technical means by which, after having established the released condition in one
flooding zone, only the output(s) to the actuators of other flooding zones shall be automatically disabled. The
disablement shall be indicated as the disabled condition of the flooding zone(s) (see 4.16).
4.29.2 All flooding zones shall be selectable to prevent the release of the extinguishing media.
4.29.3 The selection is restricted to access level 3. The selected combinations shall be identifiable at access
level 1, 2 or 3.
4.29.4 Received input triggering signals for (a) flooding zone(s), where the release of the extinguishing media for
the flooding zone(s) is prevented, shall be indicated as the activated condition of the flooding zone(s) (see 4.9).
4.29.5 The re-enablement of automatically disabled actuators shall only be possible after the e.c.d. has been
reset.
4.30 Activation of alarm devices with different signals (Option with requirements)
NOTEThis subclause relates to 4.3.2 u).
4.30.1 The e.c.d. may provide output(s) to alarm devices with at least two different signals, if the e.c.d. has the
facility to delay the extinguishing signal (see 4.17 and 4.20.3 b)).
4.30.2 The signal during the pre-discharge warning time shall be intermittent and the signal for the released
condition shall be continuous.
5 Design requirements
5.1 General
5.1.1 The following subclauses describe requirements of the mechanical, electrical and software design.
5.1.2 Compliance of the e.c.d. with this standard cannot be fully verified by functional testing because of the
impracticability of testing all possible combinations and of determining long-term reliability. In order that a
verification of the design can be achieved, it is necessary for the test organisation to assess the design.
5.1.3 The manufacturer shall declare that the design had been carried out in accordance with an appropriate
factory production control system.
Within this factory production control system a set of design rules shall be incorporated and used for the design of
hardware, software and software controlled elements of the e.c.d.
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
23
5.2 Mechanical design
The e.c.d. shall be protected against environmental influences by a cabinet of suitable mechanical strength. The
cabinet shall be classified as at least
a) IP 30 as specified in EN 60529 for e.c.d. classes A and B, or
b) IP 54 as specified in EN 60529 for e.c.d. classes C and D.
5.3 Manual controls
5.3.1 All manual controls on the e.c.d. shall be clearly labelled to indicate their purpose.
5.3.2 If the e.c.d. has provision for disconnecting or adjusting the main or the standby power source, this shall be
possible at access level 3 or 4.
5.4 Visible indicators
5.4.1 General
For the indication of the required information either separate light emitting indicators as specified in 5.4.2 or
alphanumeric displays as specified in 5.4.3 shall be used (see annex A).
5.4.2 Indications by means of separate light emitting indicators
5.4.2.1 All compulsory light emitting indicators shall be testable by manual operation at access level 1 or 2.
5.4.2.2 All light emitting indicators at access level 1 shall be clearly labelled to indicate their purpose.
Labels shall be readable at a distance of 0,8 m at an ambient light intensity between 100 lx and 500 lx.
5.4.2.3 Indications from the light emitting indicators in 5.4.2.1 and 5.4.2.2 shall be visible at any angle within
22,5 ° from a line with its origin in the centre of the light emitting indicator and perpendicular to its mounting surface
at a distance of 3 m at an ambient light intensity up to 500 lx.
5.4.2.4 Where the same light emitting indicator is used for the indication of fault and disablement of
transmission paths fault warning shall be indicated by flashing and disablement by steady lights.
5.4.2.5 Where flashing indications are used the on/off period shall each be not less than 0,25 s. The
frequencies of flash shall be:
a) for indicators of activated condition, not less than 1 Hz;
b) for indicators of fault, not less than 0,2 Hz.
5.4.3 Indications by means of alphanumeric displays
5.4.3.1 Where an alphanumeric display is used to indicate required information additional general light emitting
indicators for the "Activated Condition", "Released Condition", "Fault Warning Condition", "Disabled Condition" and
"Blocked Condition" shall be provided.
5.4.3.2 The alphanumeric display should consist at least of a sufficient number of fields to be capable of
indicating all released flooding zones simultaneously. If the alphanumeric display does not consist of a sufficient
number of fields to be capable of indicating all released flooding zones simultaneously, the released flooding zones
shall be indicated by separate light emitting indicators.
5.4.3.3 For each condition there shall be only one window, in which all of the fields relating to that condition
are grouped.
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
24
5.4.3.4 Each field shall be clearly identifiable. If not already included in the displayed information, the purpose
of the indication of a field shall be clearly labelled.
5.4.3.5 A field shall consist at least of:
-  16 characters, where the display of information uses a cross reference to other information to identify the
location;
-  40 characters, where the display is intended to include the complete information on the location.
5.4.3.6 At any time during the "Activated Condition" and the "Released Condition" it shall be possible to
display suppressed information, which is not currently indicated, by manual operation at access level 1. Reversion
to the indication of the released flooding zones shall occur between 15 s and 30 s after the last interrogation.
5.4.3.7 A window shall be clearly identifiable and distinguishable from other windows. A window may be
realised by subdivision of a larger display e.g. a screen. Such a subdivision may be realised either by mechanical
separation (frames) or by software (windows).
5.4.3.8 If an alphanumeric display consists of elements or segments, a failure of a single element or segment
shall not affect the correct interpretation of the displayed information.
5.4.3.9 Where alphanumeric displays are used the angle in which the information can be read relative to a line
perpendicular to the mounting surface of the alphanumeric display shall be at least 22,5° viewed from the side, at
least 15° viewed from above and at least 15° viewed from below.
5.4.3.10 The indications from the separate additional general indicators shall be visible in an ambient light
intensity up to 500 lx, at any angle up to 22,5° from a line through the indicator perpendicular to its mounting
surface at 3 m distance.
Information shown on an alphanumeric display shall be readable at a distance of 0,8 m at an ambient light intensity
between 5 lx and 500 lx.
5.4.3.11 No colour distinction is needed for alphanumeric displays. Where colour distinction is used the same
colour shall be used as for light emitting indicators.
5.5 Audible indicators
The minimum sound level, measured under anechoic conditions at a distance of 1 m from the cabinet, shall be at
least 60 dB(A) for the activated condition and the activation of the emergency hold or abort device and 50 dB(A) for
other indications. E.c.d.s equipped with a door have to be checked with the door closed. The signalling device may
be the same for all required audible indications.
5.6 Electrical design of components
The manufacturer has to certify in writing that all electrical components have been selected for the intended
purpose and operate within their ratings when the environmental conditions outside the cabinet of the e.c.d. comply
with EN 60721-3-3, class 3k5 for class A or class C e.c.d.s and 3k6 for class B or class D e.c.d.s.
5.7 Circuit design
5.7.1 The circuit design has to be such that a fault on any transmission path shall only affect this transmission
path and the function of the e.c.d. related to this transmission path. No other transmission path and no other
function of the e.c.d. shall be affected.
In any case, a fault on a transmission path as specified in 4.13.1 a) to g) shall not affect the function of more than
one flooding zone. Where the room and its false floor are subdivided into two flooding zones, a fault on a
transmission path may affect these two flooding zones.
5.7.2 All terminals shall have appropriate power limitation in order to ensure that in case of external short circuits
no danger exists because of heat production.
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
25
6 Additional design requirements for software controlled e.c.d.s
6.1 General
The e.c.d.s may contain elements which are controlled by software in order to fulfil the requirements of this
standard. In this case, the e.c.d.s shall comply with the requirements of this clause, as well as those of clause 5,
where relevant to the technology used.
NOTEThe following requirements are derived from the requirements for software controlled c.i.e.s (EN 54-2). Changes
were implemented, when necessary, to take into account the special functions and use of e.c.d.s.
6.2 Software design
In order to ensure the reliability of a software controlled e.c.d. the following requirements for software design shall
apply:
a) the software shall have a modular structure;
b) the design of the interfaces for manually and automatically generated data shall not permit invalid data to
cause an error in the program execution;
c) the software shall be designed to avoid the occurrence of a deadlock in the program flow.
6.3 Program monitoring
NOTESee also annex B.
6.3.1 The execution of the program shall be monitored as under 6.3.2 or 6.3.3. If routines associated with the
main functions of the program are not executed, the e.c.d. shall enter the fault warning condition and shall indicate
either or both of the following:
a) a fault, as in 4.14.1 a) and 4.14.7;
b) faults of supervised functions, as in 4.14.1 to 4.14.6, where only these functions are affected.
6.3.2 If the program executes in one processor, the execution of the routines as in 6.3.1 shall be monitored by a
monitoring device as in 6.3.4. (see 5.7.1).
6.3.3 If the program executes in more than one processor, the execution of the routines as in 6.3.1 shall be
monitored in each processor. A monitoring device as in 6.3.4 shall be associated with one or more processors and
at least one such processor shall monitor the functioning of any processor not associated with such a monitoring
device (see 5.7.1).
6.3.4 The monitoring device of 6.3.2 and 6.3.3 shall have a time base independent of that of the monitored
system. The functioning of the monitoring device, and the signalling of a fault warning, shall not be prevented by a
failure in the execution of the program of the monitored system.
6.3.5 In the event of a fault as specified in 6.3.1 a) or 6.5, those parts of the e.c.d. affected shall enter a safe
state not later than the indication of the fault (see annex B).
6.4 Storage of program and data
NOTESee also annex B.
6.4.1 All executable code and data necessary to comply with this standard shall be held in memory which is
capable of continuous, non-maintained, reliable operation for a period of at least 10 years.
6.4.2 For the program, the following requirements shall apply:
a) the program shall be held in non-volatile memory, which can only be written to at access level 4.
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
26
b) it shall be possible to identify the version reference(s) of the program at access level 3. The version
reference(s) shall be in accordance with the documentation of 6.6.1.
6.4.3 For site specific data, the following requirements shall apply:
a) the alteration of site specific data shall only be possible at access level 3 or 4;
b) the alteration of site specific data shall not affect the structure of the program;
c) the site specific data shall be given a version reference, which shall be updated when each set of alterations is
carried out;
d) it shall be possible to identify the version reference of the site specific data at access level 3;
e) if stored in volatile memory, the site-specific data shall be protected against power loss by a back-up energy
source which can only be separated from the memory at access level 4, and which is capable of maintaining
the memory contents for at least two weeks;
f) If stored in read-write memory, there shall be a mechanism which prevents the memory being written to during
normal operation at access level 1 or 2, such that its contents are protected during a failure in program
execution.
6.5 Monitoring of memory contents
The contents of the memory containing the site specific data shall be automatically checked at intervals not
exceeding 1 h. The checking device shall signal a system fault if a corruption of the memory contents is detected.
6.6 Software documentation
6.6.1 The manufacturer shall prepare documentation which gives an overview of the software design, which shall
be submitted to the testing authority together with the e.c.d. This documentation shall be in sufficient detail for the
design to be inspected for compliance with this European Standard, and shall comprise at least the following.
a) A functional description of the main program flow, including:
-  a brief description of each module and the tasks it performs;
-  the way in which the modules interact;
-  the way in which the modules are called, including any interrupt processing;
-  the overall hierarchy of the program.
The functional description of the main program flow shall be explained using a clear methodology appropriate
to the nature of the software, e.g. graphical representations of the system design, the data flows and control
flows.
b) A description of which areas of memory are used to store the program, site specific data and running data.
Where dynamic memory management is employed, a separation shall be implemented between the program,
site specific data and running data and this shall be described in connection with the method of memory
allocation.
c) A description of how the software interacts with the hardware of the e.c.d.
6.6.2 The manufacturer shall prepare and maintain detailed design documentation. This need not be submitted
to the testing authority, but shall be available for inspection in a manner which respects the manufacturer's rights of
confidentiality. This documentation shall comprise at least the following:
a) a description of each module, as it is implemented in the source code of the program, containing :
1) the name of the module;
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
27
2) the identification of the author(s);
3) the date and/or version reference;
4) a description of the tasks performed;
5) a description of the interfaces, including the type of data transfer, the valid data range, and the
checking for valid data;
b) the source code listing, including all global and local variables, constants and labels used, and sufficient
comment for the program flow to be recognised;
c) details of any software tools used in the preparation of the program (e.g. high level design tools, compilers,
assemblers).
6.7 Operation of the e.c.d. in the event of a system fault
In the event of a system fault as specified in 6.3 and 6.5 not more than one flooding zone shall be affected. Where
the room and its false floor are subdivided into two flooding zones, a system fault may affect these two flooding
zones.
7 Marking
The e.c.d. shall be marked with the following information, which shall be legible at access level 1:
a) the name or trademark of the manufacturer or supplier;
b) the model designation (type or number);
c) the environmental class (according to 4.2).
It shall be possible to identify a code or number identifying the production period of the e.c.d., at access level 2
or 3.
The marking shall be non-detachable and permanent.
Where the requirements of ZA.3 give the same information as above, the requirements of this clause 7 have been
met.
8 Documentation
8.1 The manufacturer shall prepare and maintain documentation.
8.2 The documentation shall be submitted to the testing authority and shall comprise at least the following:
a) A general description of the equipment, including a list of the features and functions relating to:
1) compulsory and optional functions with requirements of this European Standard;
2) ancillary functions not required by this European Standard;
b) A technical specification of the inputs and outputs of the e.c.d. sufficient to permit an assessment of the
mechanical, electrical and software compatibility with other components of the system, including:
1) the power requirements for recommended operation;
2) the maximum number of external connectable devices and transmission paths;
3) the maximum and minimum electrical ratings for each input and output;
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
28
4) information on the communication parameters on transmission paths;
5) recommended types of cable for each transmission path;
6) fuse ratings;
c) Installation information, including mounting instructions;
d) Operating instructions;
e) Configuring and commissioning instructions;
f) Maintenance and routine testing instructions.
8.3 The manufacturer shall also prepare, maintain and submit the following detailed description of the overall
mechanical and electrical design including:
-  the main parts of the e.c.d. and their tasks;
-  the way in which the parts interact;
-  circuit diagrams;
-  component lists;
-  layouts;
-  design drawings.
This documentation shall also comprise details of any components specific to the manufacturer (e.g. customised
integrated circuits).
8.4 All documentation normally supplied by and specified by the manufacturer for use by the end user shall be
supplied with the device and constitute part of the supply.
9 Tests
9.1 General test requirements
9.1.1 Unless otherwise stated in a test procedure, the testing shall be carried out after the test specimen has
been allowed to stabilise in the standard atmospheric conditions for testing as described in EN 60068-1 as follows:
Temperature:(15 to 35) °C
Relative humidity:(25 to 75) %
Atmospheric pressure:(860 to 1060) hPa
The temperature and humidity shall be substantially constant for each environmental test where the standard
atmospheric conditions are applied.
9.1.2 Unless otherwise stated in a test procedure, the specimen shall be mounted in its normal orientation by the
normal means of mounting indicated by the manufacturer.
9.1.3 The specimen configuration shall include at least one of each type of input and output circuits, internal
circuits and transmission paths.
9.1.4 If the test procedure requires the specimen to be in the quiescent condition, it shall be connected to a
power supply according to the requirements in EN 54-4. Unless otherwise required, the power supply shall be in
the quiescent condition. All inputs and outputs shall be connected to appropriate cables and equipment or to
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
29
dummy loads. At least one of each type of transmission path shall be maximum loaded as specified by the
manufacturer.
Test specimen(s) shall be connected with at least the following devices:
a) a triggering signal input device which simulates an f.d.a.s.;
b) a manual  triggering device;
c) an emergency hold device, if an emergency hold function is provided;
d) an emergency abort device, if an emergency abort function is provided;
e) actuator(s);
f) alarm equipment.
NOTEPeripheral devices can be kept during the tests in the standard atmospheric conditions.
9.2 Functional tests
9.2.1 The object of the functional tests is to check the compliance of the specimen with each requirement in this
standard and to demonstrate the operation of the specimen before, during and/or after the environmental
conditioning.
9.2.2 The test schedule shall be drawn up to ensure that during the functional test each type of input function
and each type of output function is exercised.
9.2.3 This shall include as a minimum:
a) Test of the Activated/Released Condition
Initiate the Activated Condition by the:
1) triggering signal input device which simulates an f.d.a.s.;
2) manual triggering device.
After each step check that the e.c.d. is in the Activated/Released Condition and that the transmission paths to
the alarm equipment and actuator(s) and ancillary device(s) are active.
Check that the set delay time is within the tolerance limits, if a delay function is provided. Check that the set
flooding time is within the tolerance limits, if a control flooding time is provided.
In a second test sequence, if an emergency hold function is provided, the emergency hold device shall be
activated:
 during the pre-discharge warning time;
 immediately after activation of the actuator(s).
Check that
 in the first case the triggering signal for the actuator(s) is delayed for the time the emergency hold device
is activated;
 in the second case the activated actuator is not influenced;
 the activation of the alarm equipment and ancillary equipment is not influenced in any case.
Check after each step that the conditions are indicated correctly.
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
30
In a third test sequence, if an emergency abort function is provided, the emergency abort device shall be
activated:
 during the quiescent condition, followed by an input triggering signal;
 during the pre-discharge warning time.
Check that the output to the actuator(s) is not activated.
Check after each step that the conditions are indicated correctly.
b) Test of Fault warning condition and monitoring;
Initiate and reset successively fault warnings corresponding at least to short circuit and interruption in the
following transmission paths to the:
 actuator(s);
 alarm equipment;
 manual triggering device(s);
 emergency hold device, if an emergency hold function is provided;
 emergency abort device, if an emergency abort function is provided;
 f.d.a.s.;
 device(s) for monitoring, if a monitoring function is provided;
 non-electrical disable device, if a separate monitoring function is provided;
In addition, initiate and reset successively fault warnings corresponding also to a loss of each of the power
sources.
Check after each step that the conditions are indicated correctly.
If an emergency hold and/or abort function is provided, check that no activation of the transmission path to the
actuator(s) is possible, when a fault is present on the transmission path to the emergency hold and/or abort
device.
c) Test of the Disabled condition;
1) Disable and re-enable the function of processing alarm signals from the transmission path to an f.d.a.s.
2) Disable and re-enable the function of processing alarm signals from the transmission path to manual
triggering device(s).
3) Disable and re-enable the transmission path to the actuator(s).
4) Disable and re-enable the transmission path to the alarm equipment, if this function is provided.
5) Disable and re-enable the transmission path to equipment outside the fire extinguishing system
(triggering of doors, ventilation shut down, plant shut down etc.), if this function is provided.
Check that the operation of the disablement controls result in the correct indication on the e.c.d.; that only
the intended parts of the system are disabled, except the disabling of the transmission path to the alarm
equipment, where the simultaneous disablement of the transmission path to the actuator(s) is required,
and that on removal of the disablement the function is restored.
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
31
9.3 Environmental tests
One or more test specimen(s) are subjected to environmental tests in accordance with EN 54-2, with the following
exceptions and amendments:
a) the fire alarm condition of EN 54-2 is considered equivalent to the activated and released condition of this
standard;
b) wherever a functional test is required, it shall be carried out in accordance with  9.1 and 9.2;
c) for e.c.d.s class B or e.c.d.s class D the test "damp heat, steady state (operational)" is replaced by the test
"damp heat, cyclic (operational)" in accordance with 9.4;
d) for e.c.d.s class C or e.c.d.s class D the test schedule is extended by an additional corrosion-test (endurance)
in accordance with 9.5;
e) in the test "cold (operational)" the test temperature during conditioning shall be:
- (-5 ± 3) °C for e.c.d.s class A or e.c.d.s class C;
- (-20 ± 3) °C for e.c.d.s class B or e.c.d.s class D.
f) In the test "vibration, sinusoidal (operational)" the acceleration amplitude shall be:
- 0,981 m/s
2
 (0,1 gn) for e.c.d.s class A or e.c.d.s class B;
- 4,905 m/s
2
 (0,5 gn) for e.c.d.s class C or e.c.d.s class D.
g) In the test "vibration, sinusoidal (endurance)" the acceleration amplitude shall be:
- 4,905 m/s
2
 (0,5 gn) for e.c.d.s class A or e.c.d.s class B;
- 9,81 m/s
2
 (1,0 gn) for e.c.d.s class C or e.c.d.s class D.
9.4 Damp heat, cyclic (Operational)
9.4.1 Object of the test
The object of the test is to demonstrate the ability of the equipment to function correctly at high relative humidity
(with condensation) which may occur for short periods in the anticipated service environment.
9.4.2 Test procedure
9.4.2.1 General
Use the test procedure described in EN 60068-2-30, using the variant 1 test cycle and controlled recovery
conditions.
9.4.2.2 Initial examination
Before conditioning, subject the specimen to the functional test.
9.4.2.3 State of the specimen during conditioning
Mount the specimen as specified in 9.1.2 and connect it to suitable power supply, monitoring and loading
equipment (see 9.1.4). The specimen shall be in the quiescent condition.
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
32
9.4.2.4 Conditioning
Apply the following severity of conditioning:
a) lower temperature: (25 ± 3) °C;
b) upper temperature (55 ± 2) °C;
c) relative humidity at lower temperature: (93 ± 3) %;
d) relative humidity at upper temperature: (93 ± 3) %;
e) number of cycles: 2.
9.4.2.5 Measurements during conditioning
Monitor the specimen during the conditioning period to detect any change in status. During the last hour of the
conditioning period, subject the specimen to the functional test.
9.4.2.6 Final measurements
After the recovery period, subject the specimen to the functional test and inspect it visually for mechanical damage
both externally and internally.
9.4.3 Requirements
During this test, the specimen shall not change status, except when such a change is a result of the functional test.
When subjected to the functional test the specimen shall respond correctly.
9.5 Sulphur dioxide (SO2) corrosion (endurance)
9.5.1 Object of the test
The object of the test is to demonstrate the ability of the equipment to withstand the corrosive effects of sulphur
dioxide as an atmospheric pollutant.
9.5.2 Test procedure
9.5.2.1 General
Use the test procedure described in prEN 60068-2-42 Test Kc, except that the conditioning shall be as described
below.
9.5.2.2 Initial examination
Before conditioning, subject the specimen to the functional test.
9.5.2.3 State of the specimen during conditioning
Mount the specimen as specified in 9.1.2 and connect it to a suitable power supply, monitoring and loading
equipment (see 9.1.4). The specimen shall not be supplied with power during the conditioning.
9.5.2.4 Conditioning
Apply the following conditioning for class C or class D e.c.d.s:
- Temperature:(25 ± 2) °C;
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
33
- Relative humidity(93 ± 3) %;
- SO2 concentration:(25 ± 5) µg/g;
- Duration:21 days.
9.5.2.5 Final measurements
Immediately after conditioning the specimen shall be subjected to a drying period of 16 h at 40 °C and a relative
humidity of maximum 50 %, followed by a recovery period of 1 h to 2 h at standard atmospheric conditions. After
this recovery period subject the specimen to the functional test and inspect it visually for mechanical damage both
externally and internally.
9.5.3 Requirements
When subjected to the functional test the specimen shall respond correctly.
10 Evaluation of conformity
10.1 General
The compliance of the component with the requirements of this European Standard shall be demonstrated by:
 initial type testing,
 factory production control by the manufacturer.
NOTEThe manufacturer is a natural or legal person, who places the component on the market under his own name.
Normally, the manufacturer designs and manufactures the component himself. As a first alternative, he may have it designed,
manufactured, assembled, packed, processed or labelled by subcontracting. As a second alternative he may assemble, pack,
process, or label ready-made products.
The manufacturer shall ensure:
 that the initial type testing in accordance with this European Standard is initiated and carried out (where
relevant, under the control of a product certification body); and
 that the component continuously complies with the initial type testing samples, for which compliance with this
European Standard has been verified.
He shall always retain the overall control and shall have the necessary competence to take the responsibility for the
component.
The manufacturer shall be fully responsible for the conformity of that component to all relevant regulatory
requirements. However, where the manufacturer uses components already shown to conform to those
requirements relevant for that component (e.g. by CE marking) the manufacturer is not required to repeat the
evaluation which led to such conformity. Where the manufacturer uses components not already shown to conform,
it is his responsibility to undertake the necessary evaluation to show conformity.
10.2 Initial type testing
10.2.1 Initial type testing shall be performed to demonstrate conformity with this European Standard.
All characteristics given in clauses 4, 5 and 6 shall be subject to this initial type testing, except as described in
10.2.3 to 10.2.5.
10.2.2 In the case of modification of the component or of the method of production (where these may affect the
stated properties), initial type testing shall be performed. All characteristics given in clauses 4, 5 and 6, which may
be changed by the modification, shall be subject to this initial type testing, except as described in 10.2.3 to 10.2.5.
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
34
10.2.3 Tests previously performed in accordance with the provisions of this standard may be taken into account
providing that they were made to the same or a more rigorous test method under the same system of attestation of
conformity on the same component or components of similar design, construction and functionality, such that the
results are applicable to the component in question.
NOTESame system of attestation of conformity means testing by an independent third party under the control of a product
certification body.
10.2.4 Components may be grouped into families where one or more characteristics are the same for all
components within that family or the test results are representative of all components within that family. In this case
not all components of the family have to be tested for the purposes of the initial type testing.
10.2.5 Where the characteristics of the component have previously been demonstrated according to the
requirements of EN 54-2, EN 54-4 and EN 60529, no further evaluation of the component, in respect of these
characteristics, is required to show conformity with this European Standard.
10.2.6 Test samples shall be representative of the normal production. If the test samples are prototypes, they
shall be representative of the intended future production and shall be selected by the manufact, urer.
NOTEIn the case of prototypes and third party certification, this means that it is the manufacturer not the third party who is
responsible for selecting the samples. During the initial inspection of the factory and of the factory production control (see 10.3),
it is verified that the component continuously complies with the initial type testing samples.
10.2.7 If the technical documentation of the test samples does not give a sufficient basis for later compliance
checks, a reference sample (identified and marked) shall remain available for this purpose.
10.2.8 Any initial type testing and its results shall be documented in a test report.
10.3 Factory production control (FPC)
10.3.1 General
The manufacturer shall establish, document and maintain an FPC system to ensure that the components placed on
the market conform with the stated performance characteristics.
If the manufacturer has the component designed, manufactured, assembled, packed, processed and labelled by
subcontracting, FPC of the subcontractor may be taken into account. Where subcontracting takes place, the
manufacturer shall retain the overall control of the component and ensure that he receives all the information that is
necessary to fulfil his responsibilities according to this European Standard. The manufacturer who subcontracts all
of his activities may in no circumstances discharge himself of his responsibilities to a subcontractor.
FPC is the permanent internal control of production exercised by the manufacturer.
All the elements, requirements and provisions adopted by the manufacturer shall be documented in a systematic
manner in the form of written policies and procedures. This production control system documentation shall ensure a
common understanding of conformity evaluation and enable the achievement of the required component
characteristics and the effective operation of the production control system to be checked.
Factory production control therefore brings together operational techniques and all measures allowing maintenance
and control of the conformity of the component with its technical specifications. Its implementation may be achieved
by controls and tests on measuring equipment, raw materials and constituents, processes, machines and
manufacturing equipment and finished components, including material properties in components, and by making
use of the results thus obtained.
10.3.2 General requirements
The FPC system should fulfil the requirements as described in the following clauses of EN ISO 9001:2000, where
applicable:
 4.2 except 4.2.1 a) Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
35
 5.1 e), 5.5.1, 5.5.2
 clause 6
 7.1 except 7.1 a), 7.2.3 c), 7.4, 7.5, 7.6
 8.2.3, 8.2.4, 8.3, 8.5.2
The FPC system may be part of a Quality Management system, e.g. in accordance with EN ISO 9001.
10.3.3 Component specific requirements
10.3.3.1 The FPC system shall
 address this European Standard; and
 ensure that the components placed on the market conform with the stated performance characteristics.
10.3.3.2 The FPC system shall include a component specific FPC- or Quality-plan, which identifies procedures
to demonstrate conformity of the component at appropriate stages, i.e.
a) the controls and tests to be carried out prior to and/or during manufacture according to a frequency laid down;
and/or
b) the verifications and tests to be carried out on finished components according to a frequency laid down.
If the manufacturer uses finished components, the operations under b) shall lead to an equivalent level of
conformity of the component as if normal FPC had been carried out during the production.
If the manufacturer carries out parts of the production himself, the operations under b) may be reduced and partly
replaced by operations under a). Generally, the more parts of the production are carried out by the manufacturer,
the more operations under b) may be replaced by operations under a). In any case the operation shall lead to an
equivalent level of conformity of the component as if normal FPC had been carried out during the production.
NOTEDepending on the specific case, it can be necessary to carry out the operations referred to under a) and b), only the
operations under a) or only those under b).
The operations under a) centre as much on the intermediate states of the component as on manufacturing
machines and their adjustment, and measuring equipment etc. These controls and tests and their frequency are
chosen based on component type and composition, the manufacturing process and its complexity, the sensitivity of
component features to variations in manufacturing parameters etc.
The manufacturer shall establish and maintain records which provide evidence that the production has been
sampled and tested. These records shall show clearly whether the production has satisfied the defined acceptance
criteria and shall be available at least for ten years. Where the component fails to satisfy the acceptance measures,
the provisions for non-conforming products shall apply, the necessary corrective action shall immediately be taken
and the components or batches not conforming shall be isolated and properly identified. Once the fault has been
corrected, the test or verification in question shall be repeated.
The results of controls and tests shall be properly recorded. The component description, date of manufacture, test
method adopted, test results and acceptance criteria shall be entered in the records under the signature of the
person responsible for the control/test. With regard to any control result not meeting the requirements of this
European Standard, the corrective measures taken to rectify the situation (e.g. a further test carried out,
modification of manufacturing process, throwing away or putting right of the component) shall be indicated in the
records.
10.3.3.3 Individual components or batches of components and the related manufacturing documentation shall
be completely identifiable and retraceable.
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
36
10.3.4 Initial inspection of factory and FPC
10.3.4.1 Initial inspection of factory and FPC shall generally be carried out when the production is already
running and the FPC is already in practice. It is, however, possible, that the initial inspection of factory and FPC is
carried out before the production is already running and/or before the FPC is already in practice.
10.3.4.2 The following shall be assessed to verify that the requirements of 10.3.2 and 10.3.3 are fulfilled:
 the FPC-documentation; and
 the factory.
In the assessment of the factory it shall be verified:
a) that all resources necessary for the achievement of the component characteristics required by this European
Standard are or will be (see 10.3.4.1) available; and
b) that the FPC-procedures in accordance with the FPC-documentation are or will be (see 10.3.4.1) implemented
and followed in practice; and
c) that the component complies or will comply (see 10.3.4.1) with the initial type testing samples, for which
compliance with this European Standard has been verified; and
d) whether the FPC system is part of a Quality Management system in accordance with EN ISO 9001 (see
10.3.2) and as part of this Quality Management system is certified and has yearly surveillance by a certification
body, who is recognised by an accreditation body which is member of the "European Co-operation for
Accreditation” and which has signed the “Multilateral agreement” (MLA) there.
10.3.4.3 All factories of the manufacturer, where for the relevant component final assembling or at least final
testing is performed, shall be assessed to verify that the conditions of 10.3.4.2 a) to c) are in place. One
assessment may cover one or more components, production lines and/or production processes. If the FPC system
covers more than one component, production line or production process, and if it is verified that the general
requirements are fulfilled then the detailed verification of the component specific FPC requirements for one
component may be taken as representative of the FPC of other components.
10.3.4.4 Assessments previously performed in accordance with the provisions of this standard may be taken
into account providing that they were made to the same system of attestation of conformity on the same component
or components of similar design, construction and functionality, such that the results may be considered applicable
to the component in question.
NOTESame system of attestation of conformity means inspection of FPC by an independent third party under the control
of a product certification body.
10.3.4.5 Any assessment and its results shall be documented in a report.
10.3.5 Continuous surveillance of FPC
10.3.5.1 All factories which have been assessed according to 10.3.4 shall be re-assessed once a year, except
as stated in 10.3.5.2.
In this case each FPC assessment shall verify a different component or production process, where applicable.
10.3.5.2 If the manufacturer provides proof of continuing satisfactory operation of his FPC system the frequency
of the re-assessment may be reduced to once every four years.
NOTE 1Sufficient proof can be the report of a certification body, see 10.3.4.2 d).
NOTE 2If the overall Quality Management system in accordance with EN ISO 9001 is well implemented (verified in the initial
assessment of factory and FPC) and continuously practised (verified in QM-audits), it can be assumed that the integrated FPC-
relevant part is well covered. On this basis, the work of the manufacturer is well controlled, so that the frequency of special FPC-
surveillance-assessments can be reduced.
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
37
10.3.5.3 Any assessment and its results shall be documented in a report.
10.3.6 Procedure for modifications
In the case of modification of the component, the method of production or the FPC system (where these may affect
the stated properties), a re-assessment of the factory and of the FPC system shall be performed for those aspects
which may be affected by the modification.
Any assessment and its results shall be documented in a report.
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
38
Annex A
(normative)
Summary of indications
A summary of indications is shown in Table A.1.
Table A.1 — Indications
Indication
Visible Information
A LL/DperALColour
Special conditions
e.c.d. is supplied with power---x---e.c.d1green---
Activated conditionxx---f.z.1red4.9.3 (two alarm signals)
Released condition---x---f.z.1red---
Transmission ‘Released condition’------xe.c.d1red4.3.2 f) (output specified for EN 54-1 (E))
Fault warning condition
x---xf.z.1yellow4.14.10 (No suppression). 4.14.1 b) (faults
related to more than 1 f.z.). 4.20 (emergency
hold 2 s).
Fault in t.p. to an f.d.a.s. or inside
the fire extinguishing system x---xt.p.1,
2
or
3
yellow---
Fault in t.p. to J or E (EN 54-1)x---xt.p.1yellow---
Power supply fault, faults of p.s.e. as
described in EN 54-4 and fault of t.p.
between e.c.d. and p.s.e.
x---xe.c.d1yellow4.13.1 j) 2) (t.p. not inside the cabinet(s) of
the e.c.d. or p.s.e. more than 0,1 m)
Earth fault affecting the function of
the e.c.d.
x---xe.c.d1yellow4.14.5 (visible indication only required, if not
covered by another fault indication)
Rupture of fuse or operation of
protective device, preventing the
operation of the e.c.d.
x---xe.c.d1yellow4.14.6 (visible indication at least as fault
indication for the supervised function)
Incorrect execution of program
and/or corruption of memory content
(only for software controlled e.c.d.)
xx---f.z.
or
e.c.d
1yellow4.14.7 (indication until manual reset and/or
another manual operation), 6.3.1 (program)
Common faultxx---e.c.d.1yellow5.3.1
Additional conditions for fault warning indications
4.14.8/4.14.9 (indication of faults, detected but not displayed because of limited space of display).
4.14.13 (output to transmit information of the fault warning condition, even if e.c.d. is deenergized).
Disabled condition---xxf.z.1yellow---
Monitoring (e.g. incorrect status of
components, loss of agent)
x---x---1yellow4.19.2 (activation of output ‘fault condition’)
Separate monitoring of non-electrical
disable device, indication of blocked
position
xx---f.z.1yellowseparate indication of blocked position and
also fault indication, see 4.19.3 (output),
(indication of incorrect position), (activation of
output ‘fault condition’)
Manual only mode---x---f.z.1yellow4.23 (output to transmit the information about
this mode)
Emergency hold device activatedxx---f.z.1yellow4.20 (indication until manual reset), (output)
Emergency abort device activatedxx---f.z.1yellow4.27 (indication until manual reset), (output)
Spare bank activation at next alarm------xBank1yellow---
Key:
A:Audible indication by audible indicator (internal buzzer)
L:Visible indication by a separate light emitting indicator
L/D:Visible indication by a separate light emitting indicator or by an alphanumeric display
AL:Access level
Colour:Colour of separate light emitting indicator
f.z.:Flooding zone
t.p.:Transmission path Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
39
Annex B
(informative)
Design requirements for software controlled e.c.d.
If a failure of program execution is detected, as specified in 6.3.1, the e.c.d. enters a safe state, as defined by the
manufacturer. It is expected that this safe state will not result in the false actioning of compulsory outputs, nor give
a false impression to a user that the e.c.d. remains operational if it is not.
It is accepted either to stop, or to automatically attempt to restart, the program execution. If there is a risk that
memory may have been corrupted, the restart procedure should check the contents of the memories, and if
necessary re-initialize running data to ensure that the e.c.d. enters a safe operating state.
Even if program execution is successfully restarted, it is important that the user is made aware of the incident. For
this reason it can be advantageous if the e.c.d. is capable of automatically recording details of the restart event. In
any event the fault indication of the failure of program execution will be latched until a manual intervention.
6.4.1 requires that all executable code and data necessary to comply with this standard will be held in memory
which is capable of continuous, unmaintained, reliable operation for a period of at least 10 years. In the existing
state of the art, memory with moving mechanical parts is not believed to be sufficiently reliable. The use of tapes, or
magnetic or optical data discs for the storage of programs and data is therefore not recommended at the time of
drafting this standard.
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
40
Annex ZA
(informative)
Clauses of this European Standard addressing the provisions of the EU
Construction Products Directive
ZA.0Scope of this annex
The scope as given in clause 1 is applicable.
ZA.1Relationship between EU Directive and this European Standard
This European Standard has been prepared under a Mandate given to CEN by the European Commission and the
European Free Trade Association.
The clauses of this European Standard shown in this annex meet the requirements of the Mandate given under the
EU Construction Products Directive (89/106).
Compliance with these clauses confers a presumption of fitness of the construction products covered by this
European Standard for their intended use.
WARNING — Other requirements and other EU Directives, not affecting the fitness for intended use may be
applicable to a construction product falling within the scope of this standard.
NOTEIn addition to any specific clauses relating to dangerous substances contained in this standard, there may
be other requirements applicable to the products falling within its scope (e.g. transposed European legislation and
national laws, regulations and administrative provisions). In order to meet the provisions of the EU Construction
Products Directive, these requirements need also to be complied with, when and where they apply. An informative
database of European and national provisions on dangerous substances is available at the Construction web site
on EUROPA (CREATE, accessed through http://europa.eu.int/comm/enterprise/construction/internal/hygiene.htm).
Construction product:  Electrical automatic control and delay device
Intended use(s): Components for use in gas extinguishing systems installed in buildings as a
complete operating system.
Table ZA.1 — Relevant Clauses
Essential characteristicsClauses in this
European Standard
Mandated levels
and/or classes
Notes
Response delay (response time)4.8-
Operational reliability4, 5, 6*,*) where relevant
Performance parameters under
fire conditions
4.3, 4.4, 4.5, 4.6-
Durability9
None
-
ZA.2Procedure for the attestation of conformity of e.c.d.s
E.c.d.s for the intended use listed shall follow the system of attestation of conformity shown in Table ZA.2 Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
41
Table ZA.2 — Attestation of conformity system
ProductIntended useLevel(s) or class(es)Attestation of
conformity system
Electrical automatic control
and delay device
Fire safety-1
System 1: See CPD annex III.2.(i), without audit testing of samples
The product certification body will certify the initial type testing of all relevant characteristics given in Table ZA.1
according to the provisions of 10.2 and for the initial inspection of the factory and of the factory production control,
and for the continuous surveillance, assessment and approval of the factory production control, all characteristics
shall be of interest to the approved body. The manufacturer shall operate a factory production control system in
accordance with the provisions of 10.3.
ZA.3CE marking
The CE marking symbol in the format specified in the EU Directive 93/68/EEC shall be shown on the component
together with the marking as specified in clause 7. In addition, the CE marking symbol shall appear on the
packaging and/or on the accompanying commercial documents, together with the following information:
-  identification number of the certification body, and
-  the last two digits of the year in which the marking was affixed, and
-  the appropriate number of the EC-certificate of conformity, and
-  the number of this standard (EN 12094-1), and
-  the type of component (i.e. electrical automatic control device or electrical automatic control and delay device),
and
-  the environmental class, and
-  the number of flooding zones,
-  per flooding zone: the type of flooding zone (e.g. CO2-high-pressure, CO2-low-pressure, inert gas, Halocarbon
gas) and provided options,
-  the response delay activated condition (i.e. ≤ 3 s),
-  the response delay triggering of outputs (i.e. ≤ 1 s).
Figure ZA.1 gives an example of the information to be given on the commercial documents.
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
42
0123
Any Co Ltd, P.O. Box 21, B1050
02
0123 - CPD – 001
EN 12094-1
Electrical automatic control and delay device
Environmental class A
6 flooding zones
Flooding zones 1 to 4:
CO2-low-pressure
Provided options:
-  Delay of extinguishing signal
-  Monitoring of status of components
-  Control of flooding time from 0 s to 300 s
-  Initiation of secondary flooding
-  Triggering of equipment outside the system
-  Control of extended discharge
Release of extinguishing media for selected flooding zones
Flooding zones 5 and 6:
CO2-high-pressure
Provided options:
-  Delay of extinguishing signal
Response delay activated conditionmaximum 3 s
Response delay triggering of outputsmaximum 1 s
Figure ZA.1 — Example CE marking information
In addition to any specific information relating to dangerous substances shown above, the component should also
be accompanied, when and where required and in the appropriate form, by documentation listing any other
legislation on dangerous substances for which compliance is claimed, together with any information required by
that legislation.
NOTEEuropean legislation without national derogations need not be mentioned.
ZA.4EC certificate and declaration of conformity
The manufacturer or his agent established in the EEA, shall prepare and retain a declaration of conformity, which
authorises the affixing of the CE marking. This declaration shall include:
-  name and address of the manufacturer, or his authorised representative established in the EEA, and the place
of production,
-  description of the component (type, identification, use), and a copy of the information accompanying the CE
marking,
-  provisions to which the component conforms (i.e. annex ZA of this EN),
-  particular conditions applicable to the use of the component [if necessary],
-  name and address (or identification number) of the certification body,
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
43
-  name of, and position held by, the person empowered to sign the declaration on behalf of the manufacturer or
of his authorised representative.
For characteristics where certification is required (system 1), the declaration shall contain a certificate of conformity
with, in addition to the information above, the following information:
-  the name and address of the certification body,
-  the certificate number,
-  conditions and period of validity of the certificate, where applicable,
-  name of, and position held by, the person empowered to sign the certificate.
The declaration and certificate shall be presented in the language(s) of the Member State of use of the component.
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIEN 12094-1:2003 (E)
44
Bibliography
EN 45002, General criteria for the assessment of testing laboratories.
EN 45011, General requirements for bodies operating product certification systems (ISO/IEC Guide 65:1996).
EN ISO 9001:2000, Quality management systems - Requirements (ISO 9001:2000).
EN ISO/IEC 17025, General requirements for the competence of testing and calibration laboratories.
EU Directive 93/68/EEC,  COUNCIL DIRECTIVE 93/68/EEC of 22 July 1993 amending Directives 87/404/EEC
(simple pressure vessels), 88/378/EEC (safety of toys), 89/106/EEC (construction products), 89/336/EEC
(electromagnetic compatibility), 89/392/EEC (machinery), 89/686/EEC (personal protective equipment),
90/384/EEC (non-automatic weighing instruments), 90/385/EEC (active implantable medicinal devices),
90/396/EEC (appliances burning gaseous  fuels), 91/263/EEC (telecommunications terminal equipment),
92/42/EEC (new  hot-water boilers fired with liquid or gaseous  fuels) and 73/23/EEC (electrical equipment
designed for use within certain voltage  limits).
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIblank
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSIBS EN
12094-1:2003
BSI
389 Chiswick High Road
London
W4 4AL
BSI—BritishStandardsInstitution
BSI is the independent national body responsible for preparing
BritishStandards. It presents the UK view on standards in Europe and at the
international level. It is incorporated by Royal Charter.
Revisions
BritishStandards are updated by amendment or revision. Users of
BritishStandards should make sure that they possess the latest amendments or
editions.
It is the constant aim of BSI to improve the quality of our products and services.
We would be grateful if anyone finding an inaccuracy or ambiguity while using
this BritishStandard would inform the Secretary of the technical committee
responsible, the identity of which can be found on the inside front cover.
Tel:+44(0)2089969000. Fax:+44(0)2089967400.
BSI offers members an individual updating service called PLUS which ensures
that subscribers automatically receive the latest editions of standards.
Buying standards
Orders for all BSI, international and foreign standards publications should be
addressed to Customer Services. Tel:+44(0)2089969001.
Fax:+44(0)2089967001. Email:orders@bsi-global.com. Standards are also
available from the BSI website at http://www.bsi-global.com.
In response to orders for international standards, it is BSI policy to supply the
BSI implementation of those that have been published as BritishStandards,
unless otherwise requested.
Information on standards
BSI provides a wide range of information on national, European and
international standards through its Library and its Technical Help to Exporters
Service. Various BSI electronic information services are also available which give
details on all its products and services. Contact the Information Centre.
Tel:+44(0)2089967111. Fax:+44(0)2089967048. Email:info@bsi-global.com.
Subscribing members of BSI are kept up to date with standards developments
and receive substantial discounts on the purchase price of standards. For details
of these and other benefits contact Membership Administration.
Tel:+44(0)2089967002. Fax:+44(0)2089967001.
Email:membership@bsi-global.com.
Information regarding online access to British Standards via British Standards
Online can be found at http://www.bsi-global.com/bsonline.
Further information about BSI is available on the BSI website at
http://www.bsi-global.com.
Copyright
Copyright subsists in all BSI publications. BSI also holds the copyright, in the
UK, of the publications of the international  standardization bodies. Except as
permitted under the Copyright, Designs and Patents Act 1988 no extract may be
reproduced, stored in a retrieval system or transmitted in any form or by any
means –  electronic, photocopying, recording or otherwise – without prior written
permission from BSI.
This does not preclude the free use, in the course of implementing the standard,
of necessary details such as symbols, and size, type or grade designations. If these
details are to be used for any other purpose than implementation then the prior
written permission of BSI must be obtained.
Details and advice can be obtained from the Copyright & Licensing Manager.
Tel:+44(0)2089967070. Fax:+44(0)2089967553.
Email:copyright@bsi-global.com.
Licensed Copy: London South Bank University, London South Bank University, Sat Jul 15 19:10:54 BST 2006, Uncontrolled Copy, (c) BSI

4161

下载说明:
1.请先分享,再下载
2.直接单击下载地址,不要使用"目标另存为"
3.压缩文件请先解压
4.PDF文件,请用PDF专用软件打开查看
5.如果资料不能下载,请联系本站

相关标准

  • BS12094-1:2003
  • BSEN50012006+A12009移动式筑路机械.安全.第1部分:一般要求
  • BSEN121512007混凝土和灰浆的制备用机械和设备.安全要求
  • BSEN1263712004混凝土结构的保护和维修用产品和系统.试验方法.注入产品的可混用性.与混凝土的可混用性
  • BSEN126912006防水柔性薄板.屋顶防水用沥青、塑料和橡胶薄板.抗冲击性的测定
  • BSEN1298312000+A12004烹饪用具.炉或炉架上使用的家用烹饪用具.第1部分:一般要求
  • BSEN7112011玩具安全第1部分:物理机械性能
  • BSEN117511998+A12010工业货车安全.电气安全.电池驱动货车的一般要求
  • BSEN52712011办公家具.工作桌和写字台.尺寸
  • BSEN120442005鞋、皮革和仿皮革产品制造机械切割和打孔机安全要求
  • 最新标准

  • 英国标准bs1199
  • 声屏障图纸
  • 钢筋进场验收记录表
  • GBT 20801.1-2006 压力管道规范 工业管道 第1部分:总则
  • GBT 20801.5-2006 压力管道规范 工业管道 第5部分:检验与试验
  • GBT 5458-2012 液氮生物容器
  • HG20613-2009钢制管法兰用紧固件(PN系列) (1)
  • 2SC2351
  • GB-T 9286-1998 色漆和清漆 漆膜的划格试验-1
  • 灭火系统规范-GB 50084
  • 热门标准

  • GB50210-2001 建筑装饰装修工程质量验收规范
  • GB/T1804-2000 一般公差线性尺寸的未注公差
  • 砖砌化粪池国标图集
  • GB/T2828.1-2012
  • GB2760-2011 食品安全国标食品添加剂使用标准
  • GB/T12706-2008 标准解读
  • HG/T20615-2009钢制管法兰 Class系列
  • GB 4706.1-2005 家用和类似部分的安全 第一部分:通用要求.pdf
  • 标准螺纹螺距对照表
  • JGJ 18-2012 钢筋焊接及验收规程
  • BS12094-1:2003
  • 本站所有信息来源于互联网,用于学习参考使用,版权归原作者所有!